Core Link+ Configuration

Core Link+ Configuration


Using this page you set up a Metacentre Core Link+
The Configuration Wizard will automatically take you through all Link+ devices in the installation, setting these up one by one.
On the top of the page, you are informed about the Address and the Name of the compressor asset.

The first step involves the Metacentre Core asking the current configuration data of the Link+ device. 
The Link+ device will respond and will send the requested data to the Metacentre Core.
The communication is taking place using the Airbus485 serial network.


During this process, a progress bar is displayed and the retrieved information is gradually displayed








If the Metacentre Core is unable to receive the requested data, an according error screen is displayed.

Once all data is gathered, the page is filled in with the current configuration data of the Link+ device.


From this moment on you can edit the Link+ device configuration.

Alarm:
When a Alarm signal is connected to the Link+ device (on DI4), this is done using a switch connecting a voltage between 24V and 240V AC/DC:
If the Alarm situation is indicated when the switch is closed, the selection has to be: "Normally Open"
If the Alarm situation is indicated when the switch is closed, the selection has to be: "Normally Closed"

When nothing is connected to DI4, the selection has to be: "Normally Closed".

Pressure sensor:
If a Pressure sensor is connected to the Link+ device, this has to be set to "Enabled", 
otherwise this has to be set to "Disabled".

Temperature sensor:
If a Temperature sensor is connected to the Link+ device, this has to be set to "Enabled", 
otherwise this has to be set to "Disabled".

    • Related Articles

    • Core Drive+ Configuration

      Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems is required to be able to successfully install and commission a Metacentre Core Drive+ product. ...
    • Address Setting Metacentre Core TAGs

      Metacentre Core TAGs come in 2 variants: Link+ and Drive+. However address setting for these is the same process, independent of the variant. The first step involves a scan executed by the Metacentre Core to detect if all expected Metacentre Core ...
    • Input Output Configuration

      The metacentre Core has 2 digital inputs and 1 digital output. This page allows to configure what the inputs and outputs are used for. DI1 used as Remote Start/Stop Options: • Enabled • Disabled Supposing the is set "Enabled", when the level on the ...
    • Control Configuration

      This page hosts the following settings Stop Control Function: Determines if and how the Metacentre Core maintains control of the compressors when it is stopped. • Return pressure control to compressors • Maintain control and continuously hold all ...
    • Sequence Rotation Configuration

      A "Sequence Rotation" event can be automatically triggered on a regular basis, using a pre-determined interval, a specific time each day, or a set day and time each week. Mode can be: Off - No rotation event defined Interval The Rotation event takes ...