Sensor Parameters

Sensor Parameters



Using this page, the Sensor parameters are set.

Second Pressure sensor: Select if a second pressure sensor is used or not. When in use, Differential Pressure will be displayed on the dashboard and Differential Pressure Level alarm can be used.
Notes
A current based 4..20mA sensor ranging 0..16 bar / 0..232 psi has to be used.
Voltage based sensors are not supported.
Temperature sensor: Select if a temperature sensor is used or not. When in use, Temperature will be displayed on the dashboard.
Notes
A PT1000 type temperature sensor has to be used
Dewpoint sensor
 Select if a dewpoint sensor is used or not. When in use, dewpoint will be displayed on the dashboard.
Notes
The sensor has to be current based, 4..20mA.
You have to provide the Dewpoint values at 4mA and at 20mA. The values in between 4mA and 20mA are obtained via linear interpolation.

External flow sensor Select if an external sensor is used or not.
When in use, flow information will be obtained via this sensor.
When not in use, flow information will be obtained via settings provided in the Asset Interface Configuration.
Notes
The sensor has to be current based, 4..20mA.
You have to provide the Flow values at 4mA and at 20mA. The values in between 4mA and 20mA are obtained via linear interpolation.

    • Related Articles

    • Asset Parameters

      This page provides the key parameters of the compressor assets in the system. In order to have the compressor system operate at optimum efficiency it is essential that these parameters are filled in precisely. Name For each Compressor Asset a name ...
    • System Parameters

      On this page, essential system parameters are set. Installation name: Provide a name for the Metacentre Core installation. This name will appear on User interface pages and on the reports. Number of compressors: the amount of compressor in the ...
    • System Pressure Parameters

      Minimum Pressure level alarm: A Pressure level which will trigger an alarm when the System Pressure drops below this level. This value is stored in Table 1. Target system pressure: The primary objective of the Metacentre Core is to control the ...
    • I'm installing a Metacentre system controller, where's the best place to locate the control pressure sensor(s)?

      The system pressure sensor (P) must be located in a position that will continuously experience pressure that is common to all compressors. Refer to Metacentre system controller Technical Manual for further guidance.
    • I've installed and commissioned the Metacentre system controller but compressors are loading and unloading erratically. What's happening?

      Metacentre system controllers load and unload a group of air compressors to maintain the configured target system pressure measured at the control pressure sensor. Site specific factors such as 'insufficient storage' or 'significant instantaneous ...

      Customer Effort & Happiness Survey