System Pressure Parameters
Minimum Pressure level alarm: A Pressure level which will trigger an alarm when the System Pressure drops below this level.

This value is stored in Table 1.
Target system pressure: The primary objective of the Metacentre Core is to control the compressor assets, ensuring that the system pressure is consistently maintained at this value, regardless of air demand.

The Unload pressure level PU as well as the Load pressure level PL are automatically calculated and stored in Table 1.
Background information: PL and PU are calculated by using a Tolerance value of 0.2 bar / 2.9 psi.
Maximum Pressure level alarm: A Pressure level which will trigger an alarm when the System Pressure goes above this level. This level should be set just below the maximum relief value and below the maximum pressure ratings of all air system components. This value remains active at all times and is independent of the Table selected.
The values between brackets “(“ and “)” indicate the range the value should reside in.
Related Articles
Asset Parameters
This page provides the key parameters of the compressor assets in the system. In order to have the compressor system operate at optimum efficiency it is essential that these parameters are filled in precisely. Name For each Compressor Asset a name ...
System Parameters
On this page, essential system parameters are set. Installation name: Provide a name for the Metacentre Core installation. This name will appear on User interface pages and on the reports. Number of compressors: the amount of compressor in the ...
Sensor Parameters
Using this page, the Sensor parameters are set. Second Pressure sensor: Select if a second pressure sensor is used or not. When in use, Differential Pressure will be displayed on the dashboard and Differential Pressure Level alarm can be used. A ...
I'm installing a Metacentre system controller, where's the best place to locate the control pressure sensor(s)?
The system pressure sensor (P) must be located in a position that will continuously experience pressure that is common to all compressors. Refer to Metacentre system controller Technical Manual for further guidance.
Metacentre P4: System Controller Manual